Danfoss AK-SM800A authenticated command execution flaw exploited, added to CISA KEV
CISA added a 2023 authenticated command execution bug in Danfoss AK-SM800A refrigeration controllers to KEV on 2026-11-25. Upgrade to 3.3 or later, remove controllers from the internet, and triage exposed units for compromise.
What you need to know
- Danfoss AK-SM800A store and refrigeration controllers on versions before 3.3 are affected, according to the CVE record.
- An attacker with a valid low-privilege web login can run arbitrary commands on the controller. CVSS 3.1 rates it 9.9.
- CISA added it to KEV as exploited on 2026-11-25. The federal due date is 2026-11-28, and forensic triage is required under BOD 26-04.
- Upgrade to 3.3 or later, ideally the latest supported release, following Danfoss's upgrade path. No controller should be reachable from the public internet.
- Do not rely on on-device logs. Compare setpoints, defrost activity and user accounts against a known-good baseline, and review network logs for external access.
What's happening
CVE-2023-25915 is an improper input validation flaw in the web interface of Danfoss AK-SM800A refrigeration and store controllers. It lets an authenticated attacker run arbitrary commands on the device 3,1. The CVE record scores it 9.9 under CVSS 3.1 3. The CVE record lists versions before 3.3 as affected, and DIVD says Danfoss recommends updating to version 3.3 3,4. The Danfoss advisory DSA-2023-08-01 was not reviewed for this brief, so these version ranges are not vendor-confirmed.
CISA added the CVE to its Known Exploited Vulnerabilities catalog on 2026-11-25, citing evidence of active exploitation 2,5. Two other AK-SM 800A flaws, CVE-2023-25914 and CVE-2025-41450, were added in the same batch 2,5. The KEV entry sets a federal due date of 2026-11-28, requires forensic triage under BOD 26-04, and lists ransomware use as unknown 1,5. CISA has not published its evidence. Danfoss has not said the flaws were exploited, and no public source gives a start date for exploitation of this specific CVE 5.
The listing follows attacks on Danfoss controllers in Europe. On 2026-10-12, CERT-FR reported numerous compromises of AK-SM and AK-SC controllers 7. Intermarché's parent company said attackers forced its stores' refrigeration into defrost mode, warming units to up to 50°C, and some stores lost stock 7. The Hacker News reports a second wave across Europe in November 6. Danfoss said most affected units were end-of-life models, but some current AK-SM 800A units running outdated firmware were also hit 7. The Hacker News reports that France has attributed the October attacks to Shahid Kaveh, an IRGC-affiliated Iranian cyber unit, and says the KEV-listed Danfoss flaws were likely used in the European attacks 5. No vendor or government source has tied CVE-2023-25915 to those attacks 5,7.
Exposure is measurable. Coalition sensors counted 1,506 unique IPs exposing a Danfoss StoreView admin panel between 2026-09-07 and 2026-10-06, and 820 of them were on French networks 8. These counts cover exposed Danfoss controllers in general, not this CVE specifically 8.
How it works
The weakness is CWE-20, improper input validation 3. DIVD's case covers several web-facing flaws in the AK-SM800A that stem from insufficient restrictions and input sanitization, and DIVD says they can lead to full system compromise 4. CISA describes the outcome as remote execution of arbitrary commands on the affected system 1,5.
The CVSS vector requires network access and a low-privilege account, with no user interaction and a changed scope 3. CISA's KEV description does not mention authentication, but the CVE record's title and vector both require a valid login to the controller's web interface 1,3. Public sources do not say how attackers get those credentials. Default or weak passwords are one possible route. Another is CVE-2025-41450, an improper authentication flaw from the same KEV batch that can expose usernames 5. No source confirms a chain.
The CVE record rates confidentiality, integrity and availability impact as high 3. Separate research by Midnight Blue on newer AK-SM 800A flaws shows what root-level code on these controllers can do: change settings, trigger defrost cycles and hide that activity from logs 6. The same research says the controllers lack secure boot, so implanted code could survive a factory reset and a firmware update 6. That research concerns different vulnerabilities, but it describes the post-exploitation risk on this hardware.
What to do
In order of priority- 1
Upgrade AK-SM800A controllers to 3.3 or later as soon as possible; 3.3 is the minimum for this CVE, so prefer the latest supported release 4,6. Follow the Danfoss upgrade path: move 3.x systems to 4.x first, and note that a controller on 5.3.x cannot be downgraded 7. From 4.0, Strict Session Control is on by default and HTTPS is mandatory 7.
- 2
Patching alone is not sufficient. Newer AK-SM 800A flaws, including CVE-2026-129713 in versions 5.4.0 and earlier, are reported as unpatched 5,6. Keep firmware current as Danfoss releases fixes 7.
- 3
Remove controllers from direct internet exposure. Danfoss says this applies to all versions, including those with Strict Mode enabled 6. CERT-FR told operators to disconnect affected controllers or filter access to them 7. Allow remote access only through a VPN; IP allowlisting is a short-term measure 6,7.
- 4
Change default passwords and enable Strict mode. Ireland's NCSC advises these steps but warns against relying on them alone 6. If you suspect compromise, change all credentials, as Germany's BSI advises 6.
- 5
Replace end-of-life AK-SM 800 (EOL since 2021) and AK-SC 355 (phased out in 2016) units. They receive no updates 7.
- 6
If mitigations cannot be applied, stop using the product, as the KEV required action states 1. Federal agencies must act by 2026-11-28 1,5.
- 7
Assume breach for internet-exposed units that ran firmware below 3.3. Perform forensic triage 1. Research on these controllers shows that implants may survive a factory reset and a firmware update 6. Consider vendor-assisted analysis or hardware replacement for units you cannot verify.
Detection
- Inventory every AK-SM800A and record its firmware version. Any unit below 3.3 is in scope 3,4. Check whether its web interface is reachable from the internet. Danfoss says no AK-SM800A should be directly exposed on any version 6.
- Validate external exposure with attack surface data. Look for Danfoss StoreView admin panels on your public IP ranges, the same interface Coalition's sensors counted 8. Include controllers reachable through 4G or 5G modems 6. No public scanner template for this CVE was confirmed.
- Treat on-device logs as unreliable. Research on these controllers shows that root-level code could hide its activity from logs 6. Use firewall, VPN, reverse-proxy and NetFlow records to find web sessions to controllers from unexpected or external sources.
- Hunt for operational anomalies in independent monitoring. Look for unscheduled defrost cycles, setpoint changes and temperature excursions, which were the visible effect of the October 2026 attacks 7. Compare user accounts, setpoints, alarm and remote-access settings against a known-good baseline 6.
- Federal agencies must perform forensic triage for this KEV entry under BOD 26-04 and assess each asset's internet exposure 1. No public IOCs were found for this CVE. The CERT-FR alert CERTFR-2026-ALE-012 was not reviewed for indicators.
Timeline
HackDefense reports AK-SM800A vulnerabilities to DIVD, which opens case DIVD-2023-00025. 4
Limited disclosure of the AK-SM800A flaws. DIVD begins scanning the internet for vulnerable instances. 4
CVE-2023-25915 published by DIVD as CNA, with a CVSS 3.1 score of 9.9. 3
DIVD begins notifying owners of vulnerable instances. 4
Attacks on Danfoss refrigeration controllers hit French supermarkets overnight. The CVE used is not stated. 7
CERT-FR reports numerous compromises of Danfoss AK-SM and AK-SC controllers. Danfoss issues statements. 7
CISA adds CVE-2023-25915 to KEV alongside CVE-2023-25914 and CVE-2025-41450. 2
KEV remediation due date for US federal agencies. 5
Sources
- 1CISA KEV entry for CVE-2023-25915CISA · Government · Nov 25, 2026
- 2CISA Adds 10 Known Exploited Vulnerabilities to CatalogCISA · Government · Nov 25, 2026
- 3CVE Record: CVE-2023-25915CVE Program / DIVD (CNA) · Database · Aug 21, 2023
- 4DIVD-2023-00025 - Multiple vulnerabilities in Danfoss AK-SM800ADIVD CSIRT · Research · Apr 25, 2024
- 5Hackers Exploit 10 Vulnerabilities Across Mitel, Juniper, Vates, and Danfoss ProductsThe Hacker News · News · Nov 26, 2026
- 6Six Unpatched Danfoss Refrigeration Controller Flaws Could Allow Remote Takeover Without LoginThe Hacker News · News · Nov 16, 2026
- 7Attackers Heat French Supermarket Fridges Up to 50°C by Hijacking Danfoss ControllersThe Hacker News · News · Oct 13, 2026
- 8Researchers warned attackers could 'defrost the food' months before French supermarkets got hitThe Register · News · Oct 15, 2026
Single source, treat with caution. Researched and drafted by the VulnDigest briefs agent from 8 sources, then checked against them by a separate review step on Nov 26, 2026.
Exploitation of this specific CVE rests on CISA's KEV listing. Danfoss has not said the flaws were exploited, and no vendor or IR firm has confirmed it.
Affected (<3.3) and fixed (3.3) versions come from the CVE record and DIVD, not the Danfoss advisory DSA-2023-08-01, which was not reviewed.
France's attribution of the October 2026 attacks to Shahid Kaveh is reported by The Hacker News. It concerns the campaign, not this CVE, so no actor is listed.
A fix exists for this CVE (3.3). The 'unpatched' reporting refers to newer, different AK-SM800A flaws, which affect current firmware.
No public proof-of-concept exploit for this CVE was confirmed.